Take charge of static and save your tester - Cabling Installation & Maintenance

Take charge of static and save your tester


Aug 1, 2001

problem

You will often find a static charge in Category 5 cable. This is due to the fact that the charge is still retained in the cable that was tested by the manufacturer. Another way the cable becomes charged is when the cable is pulled through conduit or rubbed on any solid surface. It is possible to build a charge in the cable even after the cable has been discharged. When you discharge the cable and make your punchdowns, you may still feel a shock if the charge builds up.

solution

Before you make your punchdowns or plug in your tester, "short out" all of the pairs using an 8-pin modular plug and a spade terminal. Taking this precaution of extracting the static from the cable will decrease the chance of damaging your tester or receiving a shock yourself.

procedure


  1. Create an adapter with an 8-pin modular plug and attach this adapter to one end of the cable.
  2. On the opposite end of the cable, strip three inches of the sheath from the cable so that the conductor insulation is exposed.
  3. Strip one inch of this conductor insulation and twist the ends of the exposed wires together at the end opposite the adapter. Insert these twisted wires into the barrel of a spade terminal and crimp the barrel.
  4. Remove the adapter. Now you are ready to test your cable.


An 8-pin modular plug and spade terminal may be used to extract the static charge from your cable
Click here to enlarge image

The spade terminals mentioned in this tip may be found at your local hardware store in the electronics section.

If a spade terminal is unavailable, these twisted wires may be held in place by using a "sta-kon" or wire nut or by soldering the ends.


Bob Poston is a cabling installer from King of Prussia, PA. He has spent 45 years as an installer, foreman, and supervisor working with electrical and communications cabling. He is a member of Local Union 98 IBEW.


We Recommend

Skeletons in the telecom closet: The 10 scariest things I've seen this year

The 11 biggest cabling stories of 2011

Free app calculates loss budget

Reference poster dissects 802.11n

Fiber installation courses available online

Counterfeit cable exposed

Making the switch from 62.5- to 50-micron fiber

Telecom grounding and bonding standard published by NECA and BICSI

Free poster highlights 10 fiber-safety rules


Most Popular Articles
Top Blog Posts

TIA sets objectives for 40G over twisted pair

Cancer patients miss surgery due to cable theft

Cable tech finds 500-pound bear in customer’s basement

Nearly-electrocuted copper-cable thief speaks remorsefully

House explosions, captured on video, blamed on cable theft

Modified U.S. Army drone spies on WiFi users

Turn a wiring cabinet into a liquor cabinet


Receive Free E-mail Newsletters from Cabling Installation & Maintenance

Want to hear about more articles like this one? Sign up for our free email newsletters.



Email:

First Name:

Last Name:

Promo Code (optional):

Country:

Available Newsletters:
Cabling News

Data Centers Report

Contractor Report

 


Cabling Installation & Maintenance Topic and Resource Categories:

Data CentersCabling Standards
Network CableConnectivity Technologies
Network ProtocolsIP Convergence
WirelessDesign, Installation & Testing
Current IssueArchives
Cabling BlogBuyer's Guide