Wiring a Category 5 110 block - Cabling Installation & Maintenance

Wiring a Category 5 110 block


Oct 1, 1995

Robert Y. Faber, Jr., RCDD, and Valerie Smith, EE, The Siemon Co.

Problem

Wiring 110 blocks has become difficult because of the Category 5 requirement--specified in Telecommunications Industry Association/Electronic Industries Association standard 568A--that pairs in unshielded twisted-pair cable be untwisted no more than 0.5 inch in the termination procedure.

Solution

The following procedure for terminating Category 5 UTP cable on a 110 connecting block will help ensure that the TIA standard is adhered to.

Procedure

1) Mount the 110 wiring base on a properly prepared plywood wall surface, or attach it to a rack-mount bracket for use on a crossconnect frame or equipment rack. The area behind the bracket can be used for cable management and slack storage.

2) Route the cables into place through the openings in the wiring base.

3) Remove only as much cable jacket as necessary to terminate the conductors. Remember to leave some cable slack behind the wiring base or bracket for future reterminations.

4) Lace the cable conductors into the retention slots on the 110 wiring base. Be careful not to untwist the cable pairs more than 0.5 inch for Category 5 cables (and no more than 1.0 inch for Category 4 cables).

5) Inspect the cable pairs before terminating the wires.

6) Terminate the conductors using a five-pair automatic impact tool or equivalent. This action will seat 10 conductors at one time and cut off the excess wire.

7) Place a 110 connecting block on the head of the five-pair automatic impact tool. Align the connecting block over the appropriate 110 wiring base location and terminate the connecting block onto the base. The top of the connecting block is used for termination of the crossconnect jumper wire. A termination cap may be used on the top of the connecting block.

8) Label the connections on the 110 connecting base tabs, add-on designation strips or cover.

Robert Y. Faber, Jr., RCDD, is a corporate trainer, and Valerie Smith is an electrical engineer at The Siemon Co., Watertown, CT.

Click here to enlarge image

The 110 block can be attached directly to a wall or mounted using stand-off legs to provide space behind it for cable management.


We Recommend

Skeletons in the telecom closet: The 10 scariest things I've seen this year

The 11 biggest cabling stories of 2011

Free app calculates loss budget

Reference poster dissects 802.11n

Fiber installation courses available online

Counterfeit cable exposed

Making the switch from 62.5- to 50-micron fiber

Telecom grounding and bonding standard published by NECA and BICSI

Free poster highlights 10 fiber-safety rules


Most Popular Articles
Top Blog Posts

TIA sets objectives for 40G over twisted pair

Cancer patients miss surgery due to cable theft

Cable tech finds 500-pound bear in customer’s basement

Nearly-electrocuted copper-cable thief speaks remorsefully

House explosions, captured on video, blamed on cable theft

Modified U.S. Army drone spies on WiFi users

Turn a wiring cabinet into a liquor cabinet


Receive Free E-mail Newsletters from Cabling Installation & Maintenance

Want to hear about more articles like this one? Sign up for our free email newsletters.



Email:

First Name:

Last Name:

Promo Code (optional):

Country:

Available Newsletters:
Cabling News

Data Centers Report

Contractor Report

 


Cabling Installation & Maintenance Topic and Resource Categories:

Data CentersCabling Standards
Network CableConnectivity Technologies
Network ProtocolsIP Convergence
WirelessDesign, Installation & Testing
Current IssueArchives
Cabling BlogBuyer's Guide