Avoid a patch cord "spaghetti bomb" on the front of racks - Cabling Installation & Maintenance

Avoid a patch cord "spaghetti bomb" on the front of racks


Nov 1, 1996

Victoria Trippe, Ortronics Inc.

Problem

Most cable installers take great pains to meet installation requirements and dress cables neatly at the rear of patch panels in the telecommunications closet. Unfortunately, the contractor?s work at the rear of the rack or cabinet is seldom seen. More noticeable is the patching field at the front of the rack or cabinet, which often looks as if a spaghetti bomb had exploded between the patch panel and the hub(s).

Solution

One way to avoid this problem is to install wire managers above and below each patch panel and run patch cords through both top and bottom managers. When routed in this manner, cords will rarely cross over the top of each other in a spider-web fashion. This type of routing will also facilitate maintenance, troubleshooting and cable management.

Procedure

1) Install a wire manager above and below each patch panel in the closet.

2) When ready to install the patch cords, visually divide the patch panel according to port groupings. For example, divide a 24-port panel in half, divide a 48-port or larger patch panel into quarters.

3) While grouping the cords to the closest port in its section, install the cords in the patch panel.

4) Use Velcro tie-wraps to bundle the cords into neat groups (if desired).

5) When installed correctly in this manner, the cords should not overlap on the patching field, which will allow for easier identification, labeling and management.

Note: Always label termination hardware according to the tia/eia-606 administrative standard; for example, Section 6.2.4 recommends that Oan identifier be marked on each termination hardware or its label. Duplicate labeling of termination hardware located in the work area is optional.O And, for termination position labeling, Section 6.2.6 recommends that Oan identifier be recorded on each termination position label. Each termination position shall be labeled with the termination position identifier, except in cases where high termination densities make labeling impractical. In these cases, identifiers shall be assigned to each termination hardware unit and to the actual termination position identifier determined by the conventions used for that unit.O

Click here to enlarge image

Incorporate Your Company Logo into the Cable Installation

Potential customers who see your completed cabling installation may recognize good-quality work but may not know who performed the work or how to contact you. Using filler panels, which can be silk-screened or engraved, and preprinted labels at work-area telecommunications outlets, you can exhibit pride in your craftsmanship, while leaving a highly visible business card.

Screen print or engrave blank filler panels with your company`s logo, telephone number and address.

Have paper or adhesive-backed labels printed with your company`s logo and telephone number to fit faceplate labeling slots.

Install filler panels at the top of racks and cabinets in main crossconnects, intermediate crossconnects and telecommunications closets.

Install telecommunications outlet and connector labels in work-area faceplates with your company card.

Click here to enlarge image

To manage patch cords in the wiring-closet rack, install wire managers above and below each patch panel.

Victoria Trippe, registered communications distribution designer (rcdd), is a senior systems trainer at Ortronics Inc., Pawcatuck, CT.


We Recommend

Skeletons in the telecom closet: The 10 scariest things I've seen this year

The 11 biggest cabling stories of 2011

Free app calculates loss budget

Reference poster dissects 802.11n

Fiber installation courses available online

Counterfeit cable exposed

Making the switch from 62.5- to 50-micron fiber

Telecom grounding and bonding standard published by NECA and BICSI

Free poster highlights 10 fiber-safety rules


Most Popular Articles
Top Blog Posts

TIA sets objectives for 40G over twisted pair

Cancer patients miss surgery due to cable theft

Cable tech finds 500-pound bear in customer’s basement

Nearly-electrocuted copper-cable thief speaks remorsefully

House explosions, captured on video, blamed on cable theft

Modified U.S. Army drone spies on WiFi users

Turn a wiring cabinet into a liquor cabinet


Receive Free E-mail Newsletters from Cabling Installation & Maintenance

Want to hear about more articles like this one? Sign up for our free email newsletters.



Email:

First Name:

Last Name:

Promo Code (optional):

Country:

Available Newsletters:
Cabling News

Data Centers Report

Contractor Report

 


Cabling Installation & Maintenance Topic and Resource Categories:

Data CentersCabling Standards
Network CableConnectivity Technologies
Network ProtocolsIP Convergence
WirelessDesign, Installation & Testing
Current IssueArchives
Cabling BlogBuyer's Guide