Designing UTP cable plant - Cabling Installation & Maintenance

Designing UTP cable plant


Jan 1, 1997

Q: In my new position, I will be responsible for designing and overseeing the implementation of the UTP cable plant for a new 2000- to 4000-station network. My objective is to design a structured system that is flexible and also conforms to industry standards. I reviewed the tia/eia-568a standard and have put together a proposed design.

Although the patch panel is in the same closet as the termination blocks and equipment, I consider the cables between the patch panel and termination blocks to be "backbone" cables. Using this logic and the backbone hierarchical topology model in tia/eia-568a, I believe the design is acceptable as long as cable-distance requirements are observed. Several co-workers think the design does not comply with the standard, and I need an expert opinion. Can you advise if this design complies with tia/eia-568a?

John Meisner, Penn State M.S. Hershey Medical Center

Hershey, PA

A: According to tia/eia-568a, the function of backbone cabling is to provide interconnections between telecommunications closets, equipment rooms and entrance facilities within the telecommunications cabling system structure.

The cable between the outlet/connector and the horizontal crossconnect is horizontal cable, and the cable between the hub and the patch panel is an equipment cable. The cable between the second connecting block and the patch panel--the one you designate "backbone" cable--is not covered in tia/eia-568a.

The tia/eia-568a standard requires that backbone cabling use a hierarchical star topology and that it have no more than two hierarchical levels of crossconnects.

This means that each horizontal crossconnect in a telecommunications closet is cabled to a main crossconnect or an intermediate crossconnect, then to a main crossconnect. Following your logic one step further, the hub is now either a main crossconnect or an intermediate crossconnect--which it is not.

Now that we have worked through the logic and standard arguments, I think what you really want is to design a cabling system that will provide a robust channel. The channel described in Annex E, section E.2, of tia/eia-568a includes a work-area cord, a telecommunications outlet/connector, up to 90 meters of balanced UTP cable, an optional transition connection close to the work area, a horizontal crossconnect consisting of two connecting blocks or patch panels in the telecommunications closet, and an equipment cord.

The design in your diagram adds a third piece of connecting hardware and another cord or cable .

You should either terminate the horizontal cable on a connecting block or a patch panel and patch directly into the hub or use an equipment cable with an 8-pin modular connector only on one end, terminating the unconnectorized pairs on a connecting block or on the back side of a patch panel and then jumper or patch block to block or patch panel to panel (see crossconnect diagram above).

This does not mean that your design would not support some or even most applications available today, but applications of the future are being designed assuming that there is an Annex E-compliant channel available.

Donna Ballast is a communications analyst at the University of Texas

at Austin and a bicsi registered communications distribution designer (rcdd). Questions can be sent to her at Cabling Installation & Maintenance or at PO Drawer 7580, University of Texas, Austin, TX 78713; tel: (512) 471-0112, fax: (512) 471-8883, e-mail: ballast@utexas.edu.


We Recommend

Skeletons in the telecom closet: The 10 scariest things I've seen this year

The 11 biggest cabling stories of 2011

Free app calculates loss budget

Reference poster dissects 802.11n

Fiber installation courses available online

Counterfeit cable exposed

Making the switch from 62.5- to 50-micron fiber

Telecom grounding and bonding standard published by NECA and BICSI

Free poster highlights 10 fiber-safety rules


Most Popular Articles
Top Blog Posts

TIA sets objectives for 40G over twisted pair

Cancer patients miss surgery due to cable theft

Cable tech finds 500-pound bear in customer’s basement

Nearly-electrocuted copper-cable thief speaks remorsefully

House explosions, captured on video, blamed on cable theft

Modified U.S. Army drone spies on WiFi users

Turn a wiring cabinet into a liquor cabinet


Receive Free E-mail Newsletters from Cabling Installation & Maintenance

Want to hear about more articles like this one? Sign up for our free email newsletters.



Email:

First Name:

Last Name:

Promo Code (optional):

Country:

Available Newsletters:
Cabling News

Data Centers Report

Contractor Report

 


Cabling Installation & Maintenance Topic and Resource Categories:

Data CentersCabling Standards
Network CableConnectivity Technologies
Network ProtocolsIP Convergence
WirelessDesign, Installation & Testing
Current IssueArchives
Cabling BlogBuyer's Guide