Consolidation points in ceilings - Cabling Installation & Maintenance

Consolidation points in ceilings


Aug 1, 1997

Q: Could you clarify the specific points from tsb-75 about consolidation points? The March 1997 cover of Cabling Installation & Maintenance shows a consolidation point being installed in the ceiling; I was led to believe that you should not install them there because of access problems.

Richard E. Henderson, rcdd

Krone Inc.

Englewood, CO

A: I strongly agree with you that consolidation points should not be installed in ceiling spaces, but unfortunately a majority of the voting members of TR-41.8.1, the authors of tsb-75, did not. The following is the list of specific points from tsb-75, Section 6, that you requested:

- Consolidation points shall not be located in any obstructed area.

- Consolidation points shall be located in fully accessible, permanent locations such as building columns and permanent walls.

- Consolidation points shall not be installed in furniture unless that unit of furniture is permanently secured to the building structure.

- Consolidation-point accessibility and marking should follow tia/eia-568a, Section G.2.3, which states: "A consolidation point should be readily accessible and its location visibly marked, allowing for ease of routine maintenance and reconfiguration."

How "fully accessible" or "readily accessible" is a box in the ceiling? I still remember the countless hours that I have spent above the ceiling, tugging on 25-pair cables and trying to listen for "the can" to rattle. The proponents of these products will tell you that cannot happen now, not if you follow the standard and label everything. The can locations were labeled, but over time the tiles were not put back in their original locations, or had to be changed because of all the dirty fingerprints, or the label fell off the T-bar, or worse yet, the can was moved by another building trade needing access to their equipment.

Donna Ballast is a communications analyst at the University of Texas at Austin and a bicsi registered communications distribution designer (rcdd). Questions can be sent to her at Cabling Installation & Maintenance or at PO Drawer 7580, University of Texas, Austin, TX 78713; tel: (512) 471-0112, fax: (512) 471-8883, e-mail: ballast@utexas.edu.


We Recommend

Skeletons in the telecom closet: The 10 scariest things I've seen this year

The 11 biggest cabling stories of 2011

Free app calculates loss budget

Reference poster dissects 802.11n

Fiber installation courses available online

Counterfeit cable exposed

Making the switch from 62.5- to 50-micron fiber

Telecom grounding and bonding standard published by NECA and BICSI

Free poster highlights 10 fiber-safety rules


Most Popular Articles
Top Blog Posts

TIA sets objectives for 40G over twisted pair

Cancer patients miss surgery due to cable theft

Cable tech finds 500-pound bear in customer’s basement

Nearly-electrocuted copper-cable thief speaks remorsefully

House explosions, captured on video, blamed on cable theft

Modified U.S. Army drone spies on WiFi users

Turn a wiring cabinet into a liquor cabinet


Receive Free E-mail Newsletters from Cabling Installation & Maintenance

Want to hear about more articles like this one? Sign up for our free email newsletters.



Email:

First Name:

Last Name:

Promo Code (optional):

Country:

Available Newsletters:
Cabling News

Data Centers Report

Contractor Report

 


Cabling Installation & Maintenance Topic and Resource Categories:

Data CentersCabling Standards
Network CableConnectivity Technologies
Network ProtocolsIP Convergence
WirelessDesign, Installation & Testing
Current IssueArchives
Cabling BlogBuyer's Guide