Innerduct for fiber? - Cabling Installation & Maintenance

Innerduct for fiber?


Jan 1, 1998

Q: Should fiber-optic horizontal cable be installed in innerduct? In the environment in question, plenum fiber-optic cable is being installed between a data closet and a classroom. As you know, educational facilities want quality jobs but are mindful of the costs.

Some of my colleagues favor installing innerduct in the route to protect the fiber and for ease of placement. They cite BICSI`s (Tampa, FL) Cabling Install-ation Manual. Others argue that a fiber-optic cable properly routed through a ceiling cable-support system is as secure as the innerduct system.

But the added expense of a double plenum hit--plenum innerduct and plenum fiber--is not justified because this job is not a multi-tenant environment, in which each customer uses a different vendor and installs different cables. An outside opinion would be refreshing.

LaDonna Hagler

Southwestern Bell

Dallas, TX

A: I believe that prudent use of short pieces of plenum optical-fiber raceway in ducts, plenums, or other spaces used for environmental air is good cable- management design. However, providing a listed plenum optical-fiber raceway from the telecommunications closet to the work-area outlet will continue to make fiber-to-the-desk unnecessarily cost-prohibitive. At 160-pounds force (lbf) pulling tension, optical-fiber cable has always been a more robust medium than the more widely deployed unshielded twisted-pair cable, at 25-lbf pulling tension.

Although BICSI`s Cabling Installation Manual is a good place to start, it is not an industry standard. It did not go through the same industry-wide balloting and comment resolution process that the standards of the Telecommunications Industry Association and Electronic Industries Association (tia/eia--Arlington, VA) are held to. Any comments or questions regarding this manual or other BICSI manuals should be directed to John Siemon of The Siemon Co., chair of the BICSI Engineering and Methods Committee, at John_Siemon@siemon.com.

Donna Ballast is a communications analyst at The University of Texas at Austin and a BISCI registered communications distribution designer (RCDD). Questions can be sent to her at:

Cabling Installation & Maintenance or at PO Drawer 7580,

The University of Texas,

Austin, TX 78713;

tel: (512) 471-0112,

fax: (512) 471-8883,

e-mail: ballast@utexas.edu.


We Recommend

Skeletons in the telecom closet: The 10 scariest things I've seen this year

The 11 biggest cabling stories of 2011

Free app calculates loss budget

Reference poster dissects 802.11n

Fiber installation courses available online

Counterfeit cable exposed

Making the switch from 62.5- to 50-micron fiber

Telecom grounding and bonding standard published by NECA and BICSI

Free poster highlights 10 fiber-safety rules


Most Popular Articles
Top Blog Posts

TIA sets objectives for 40G over twisted pair

Cancer patients miss surgery due to cable theft

Cable tech finds 500-pound bear in customer’s basement

Nearly-electrocuted copper-cable thief speaks remorsefully

House explosions, captured on video, blamed on cable theft

Modified U.S. Army drone spies on WiFi users

Turn a wiring cabinet into a liquor cabinet


Receive Free E-mail Newsletters from Cabling Installation & Maintenance

Want to hear about more articles like this one? Sign up for our free email newsletters.



Email:

First Name:

Last Name:

Promo Code (optional):

Country:

Available Newsletters:
Cabling News

Data Centers Report

Contractor Report

 


Cabling Installation & Maintenance Topic and Resource Categories:

Data CentersCabling Standards
Network CableConnectivity Technologies
Network ProtocolsIP Convergence
WirelessDesign, Installation & Testing
Current IssueArchives
Cabling BlogBuyer's Guide