The myth of connecting hardware power-sum performance claims - Cabling Installation & Maintenance

The myth of connecting hardware power-sum performance claims


Sep 1, 1998

Valerie Rybinski

The Siemon Co.

Vendors who claim that their connecting hardware is "power-sum" compliant appear to offer a performance advantage over those vendors who specify their hardware`s worst-case pair-to-pair near- end crosstalk (NEXT) performance. Although perfectly applicable to the specification of cabling and cabling performance, some power-sum claims for connecting hardware are ill-founded and could result in end-users getting less than what they bargained for.

Historically, the rationale behind specifying power-sum near-end crosstalk (PS-NEXT) requirements for connecting hardware was based on the thinking that if power-sum channels are going to be specified, then power-sum components should be specified as well. Although there is some logic behind the statement, significant supporting data exists to demonstrate that a worst-case power-sum measurement is difficult, if not impossible, to apply consistently and accurately to connecting hardware qualification. To make matters worse, because a test algorithm for worst-case power-sum data collection does not exist, different manufacturers` power-sum claims may mean different things.

For example, a company can easily claim power-sum Category 5 performance for a connector based on data collected at one frequency point (such as 100 megahertz), measured in one test orientation (from the plug orientation only), with a high-end test plug rather than the full test-plug range specified in the TIA/EIA-568a Commercial Building Telecommunications Cabling Standard, or after testing in only one termination mode, such as the differential mode.

No basis in standards

A manufacturer must analyze hundreds of test configurations before reasonably claiming measured power-sum performance. Even then, there is no assurance that the worst-case test configuration has been evaluated. The PN-2948 Connecting Hardware Task Group of the Telecommunications Industry Association (Arlington, VA) recently addressed these concerns by specifying a worst-case pair-to-pair next characterization for connecting hardware that is sufficent to ensure channel and basic link ps-next performance. In fact, until such time as a power-sum test algorithm is defined, claims of "power-sum compliant" connecting hardware are not supported by industry standards.

The good news is that you can easily calculate an equivalent worst-case pair-to-pair next margin that correlates to Category 5 power-sum performance. By assessing the statistical relationship between pair-to-pair next values in connecting hardware, the tia PN-3727 utp Systems Task Group has determined that a common and differential mode pair-to-pair next margin of 3 decibels over Category 5 requirements is sufficient to ensure Category 5 power-sum performance.

In specifying connecting hardware, be sure to note worst-case guaranteed pair-to-pair next performance and verify that measurement margins are based on testing with and without common-mode terminations. Although power-sum claims may sound appealing, the power-sum algorithm tends to mask worst-case pair-to-pair performance for components that may prove cumulative--for example, two worst-case pair-to-pair combinations that are in a series and interact adversely in a channel configuration. Claims of connecting hardware power-sum performance are not sufficient to ensure proper channel near-end crosstalk performance.


We Recommend

Skeletons in the telecom closet: The 10 scariest things I've seen this year

The 11 biggest cabling stories of 2011

Free app calculates loss budget

Reference poster dissects 802.11n

Fiber installation courses available online

Counterfeit cable exposed

Making the switch from 62.5- to 50-micron fiber

Telecom grounding and bonding standard published by NECA and BICSI

Free poster highlights 10 fiber-safety rules


Most Popular Articles
Top Blog Posts

TIA sets objectives for 40G over twisted pair

Cancer patients miss surgery due to cable theft

Cable tech finds 500-pound bear in customer’s basement

Nearly-electrocuted copper-cable thief speaks remorsefully

House explosions, captured on video, blamed on cable theft

Modified U.S. Army drone spies on WiFi users

Turn a wiring cabinet into a liquor cabinet


Receive Free E-mail Newsletters from Cabling Installation & Maintenance

Want to hear about more articles like this one? Sign up for our free email newsletters.



Email:

First Name:

Last Name:

Promo Code (optional):

Country:

Available Newsletters:
Cabling News

Data Centers Report

Contractor Report

 


Cabling Installation & Maintenance Topic and Resource Categories:

Data CentersCabling Standards
Network CableConnectivity Technologies
Network ProtocolsIP Convergence
WirelessDesign, Installation & Testing
Current IssueArchives
Cabling BlogBuyer's Guide