Install wooden spacers between racks


Dec 1, 1998

Anthony DiGregorio, TelVue Corp.

Problem

A change from circuit-switching equipment to packet-switching equipment has left you with too many plugs and too few outlets in your telecommunications closet. You are now tasked with keeping AC power cords a safe distance away from data cords.

Solution

Install wooden spacers between equipment racks, and mount AC outlet strips onto the spacers.

Procedure

1) Cut two pieces of lumber (2 x 4, 2 x 6, 2 x 8, or whatever size suits your needs) so they are the same height as your equipment racks.

2) Fasten the two pieces of lumber together using drywall screws to form the spacer.

3) Drill holes on each side of the spacer so that you can fasten the spacer to the racks using bolts.

4) Paint the spacer with fire-retardant paint in a color that matches the racks.

5) Fasten the spacer to the racks using bolts and the holes you drilled in the spacer.

6) Have a qualified electrician hardwire outlet strips onto the spacer. Make sure you specify outlet strips that provide space between the outlets; some equipment requires AC or DC adapters, which have transformers.

7) Develop a wiring path that has power cords routed toward the outlet side of the bay and data cords routed in the opposite direction.

8) You can also use the front of the spacer to route patch cords, hang a telephone, or post paperwork.

Anthony DiGregorio is a technical specialist with TelVue Corp. (Mt. Laurel, NJ). This tip was submitted for the Cabling Installer Tips` Contest at Cabling Installation Expo `98, held in October in Atlanta, GA.

Click here to enlarge image

In both racks, all power connections are routed to the left and all data connections routed to the right. Note that the outlet strips are placed on the right half of the spacer to accommodate this cord-routing path.

Click here to enlarge image

You can place rings on the left side of the spacer to accommodate data cords.


We Recommend

Skeletons in the telecom closet: The 10 scariest things I've seen this year

The 11 biggest cabling stories of 2011

Free app calculates loss budget

Reference poster dissects 802.11n

Fiber installation courses available online

Counterfeit cable exposed

Making the switch from 62.5- to 50-micron fiber

Telecom grounding and bonding standard published by NECA and BICSI

Free poster highlights 10 fiber-safety rules


Most Popular Articles
Top Blog Posts

TIA sets objectives for 40G over twisted pair

Cancer patients miss surgery due to cable theft

Cable tech finds 500-pound bear in customer’s basement

Nearly-electrocuted copper-cable thief speaks remorsefully

House explosions, captured on video, blamed on cable theft

Modified U.S. Army drone spies on WiFi users

Turn a wiring cabinet into a liquor cabinet


Receive Free E-mail Newsletters from Cabling Installation & Maintenance

Want to hear about more articles like this one? Sign up for our free email newsletters.



Email:

First Name:

Last Name:

Promo Code (optional):

Country:

Available Newsletters:
Cabling News

Data Centers Report

Contractor Report

 


Cabling Installation & Maintenance Topic and Resource Categories:

Data CentersCabling Standards
Network CableConnectivity Technologies
Network ProtocolsIP Convergence
WirelessDesign, Installation & Testing
Current IssueArchives
Cabling BlogBuyer's Guide