Planning for slack in the telecommunications closet


Jan 1, 1999

Brant Hylton, Novartis Crop Protection Inc.

problem

It is often difficult to plan and provide for slack cable in the telecommunications closet (TC) that will offer the flexibility needed to make future cabling-system changes.

solution

By installing a section of flexible cable tray on the closet wall, you can provide an inexpensive, easily accessible, protected length of slack cable to your horizontal or backbone cable runs. This arrangement will make future cabling changes easier and less time-consuming.

procedure

1) Install a 5-foot section of flexible cable tray to the closet wall, which should be lined with 3/4-inch plywood. Install the tray as close as possible to the rack it will serve. Mount the cable tray to the wall using standoff brackets that will allow you to route cable ties between the tray and wall. Also remember to provide a cable tray that will be large enough to easily handle more cables in the future.

2) Starting at the top of the tray, place a cable or multiple cables into the tray using tie wraps to hold them in place. At the bottom of the tray, loop the cables back up to the top of the tray. Make sure that you provide for the minimum amount of bend radius required for the cables that will be placed into the tray.

3) Route cables to the rack that you are serving. Attach the flexible cable-tray cover over the top of the cable tray.

4) When you need to access the slack cables, remove the cover and cut the cable ties. Make any changes necessary, then replace the cables in the tray and reattach the cable ties and cover.

Click here to enlarge image

You should attach the flexible cable tray as close as possible to the rack that it will serve. Once you have the tray in place against the TC wall, attach a removable cover so you can access the cables when necessary (see inset).

Brant Hylton, registered communications distribution designer (rcdd), is a network engineer III with Novartis Crop Protection Inc. (Greensboro, NC). This tip was submitted for the Cabling Installer Tips` Contest at Cabling Installation Expo `98, held last October in Atlanta, GA.


We Recommend

Skeletons in the telecom closet: The 10 scariest things I've seen this year

The 11 biggest cabling stories of 2011

Free app calculates loss budget

Reference poster dissects 802.11n

Fiber installation courses available online

Counterfeit cable exposed

Making the switch from 62.5- to 50-micron fiber

Telecom grounding and bonding standard published by NECA and BICSI

Free poster highlights 10 fiber-safety rules


Most Popular Articles
Top Blog Posts

TIA sets objectives for 40G over twisted pair

Cancer patients miss surgery due to cable theft

Cable tech finds 500-pound bear in customer’s basement

Nearly-electrocuted copper-cable thief speaks remorsefully

House explosions, captured on video, blamed on cable theft

Modified U.S. Army drone spies on WiFi users

Turn a wiring cabinet into a liquor cabinet


Receive Free E-mail Newsletters from Cabling Installation & Maintenance

Want to hear about more articles like this one? Sign up for our free email newsletters.



Email:

First Name:

Last Name:

Promo Code (optional):

Country:

Available Newsletters:
Cabling News

Data Centers Report

Contractor Report

 


Cabling Installation & Maintenance Topic and Resource Categories:

Data CentersCabling Standards
Network CableConnectivity Technologies
Network ProtocolsIP Convergence
WirelessDesign, Installation & Testing
Current IssueArchives
Cabling BlogBuyer's Guide