Grounding shielded backbone cable - Cabling Installation & Maintenance

Grounding shielded backbone cable


Nov 1, 1999

Q: At a Veterans Administration Hospital in Helena, MT, we ran a 24-AWG, 1800-pair copper backbone shielded cable. Should both ends on the cable be bonded to ground? This riser cable is installed in a 4-inch steel conduit from closet to closet, and the conduit is grounded at both ends. We grounded only one end of the cable shield.

Edward A. Hartman

DBA Phone Factory

Helena, MT

A: ANSI/TIA/EIA-607, Section 6.3.2, says, "In buildings where the backbone cable incorporates a shield or metallic member, this shield or metallic member shall be bonded to the tmgb/tgb [telecommunications main grounding busbar/telecommunications grounding busbar]."

In an intrabuilding backbone cable with an overall cable shield, the shield acts as the coupled bonding conductor (CBC). The CBC, like a telecommunications bonding backbone, not only provides equalization of potential but also, because of the close proximity to the conductors, provides protection through electromagnetic coupling with the telecommunications cable. To work properly, the CBC must be directly connected to the ground at the protector end (the TMGB) and to the ground at the equipment end (the TGB). Many equipment manufacturers require a CBC between their equipment and exposed circuit protectors.

Donna Ballast is a communications analyst at the University of Texas at Austin and a bicsi registered communications distribution designer (rcdd). Questions can be sent to her at Cabling Installation & Maintenance or at PO Drawer 7580, the University of Texas, Austin, TX 78713; tel: (512) 471-0112, fax: (512) 471-8883, e-mail: ballast@utexas.edu.


We Recommend

Skeletons in the telecom closet: The 10 scariest things I've seen this year

The 11 biggest cabling stories of 2011

Free app calculates loss budget

Reference poster dissects 802.11n

Fiber installation courses available online

Counterfeit cable exposed

Making the switch from 62.5- to 50-micron fiber

Telecom grounding and bonding standard published by NECA and BICSI

Free poster highlights 10 fiber-safety rules


Most Popular Articles
Top Blog Posts

TIA sets objectives for 40G over twisted pair

Cancer patients miss surgery due to cable theft

Cable tech finds 500-pound bear in customer’s basement

Nearly-electrocuted copper-cable thief speaks remorsefully

House explosions, captured on video, blamed on cable theft

Modified U.S. Army drone spies on WiFi users

Turn a wiring cabinet into a liquor cabinet


Receive Free E-mail Newsletters from Cabling Installation & Maintenance

Want to hear about more articles like this one? Sign up for our free email newsletters.



Email:

First Name:

Last Name:

Promo Code (optional):

Country:

Available Newsletters:
Cabling News

Data Centers Report

Contractor Report

 


Cabling Installation & Maintenance Topic and Resource Categories:

Data CentersCabling Standards
Network CableConnectivity Technologies
Network ProtocolsIP Convergence
WirelessDesign, Installation & Testing
Current IssueArchives
Cabling BlogBuyer's Guide