Requirements for plenum- and riser-rated cable

June 1, 1999
Q: As cabling contractors, we run into requests for proposals that require plenum or polyvinyl chloride (pvc)-jacketed cable. Most building inspectors are consistent in what they require, but fire inspectors seem to vary with their moods. We have been asked, primarily by our customers, what the requirements are for running pvc-jacketed cable or riser-rated cable into a building. I am aware that, according to the National Electrical Code (nec), no pvc-jacketed cable can run in an air-return space

Q: As cabling contractors, we run into requests for proposals that require plenum or polyvinyl chloride (pvc)-jacketed cable. Most building inspectors are consistent in what they require, but fire inspectors seem to vary with their moods. We have been asked, primarily by our customers, what the requirements are for running pvc-jacketed cable or riser-rated cable into a building. I am aware that, according to the National Electrical Code (nec), no pvc-jacketed cable can run in an air-return space for more that 50 feet, unless it is in conduit. I believe this but cannot find any documentation in the nec or tia standards. Both specifications refer to an authority called umc for exact codes and specifications, but I have been unable to find any documentation specifically stating how far and what requirements there are for this application.

Ed Kofol

Pacific States Communications

Reno, NV

A: The 50-foot rule is in nec 800-50, Listing, Marking, and Installation of Communications Wires and Cables, which says that communications cables installed in buildings shall be listed as being suitable for the purpose. There are some exceptions:

Listing is not required where the cable enters the building from the outside and is continuously enclosed in a rigid or an intermediate metal conduit.

Listing is not required where the cable enters the building from the outside and is terminated in an enclosure or on a listed primary protector and the length of the cable within the building, measured from its point of entrance, does not exceed 50 feet.

But these exceptions all address outside-plant distribution cable, not plenum- or riser-rated cable. Within the nec, there is zero tolerance for a riser-rated cable in a plenum environment. The tia standards address performance issues, but plenum- versus riser-rated cable is a safety issue.

Donna Ballast is a communications analyst at the University of Texas at Austin and a bicsi reg-istered communications distribution designer (rcdd). Questions can be sent to her at Cabling

Installation & Maintenance or at PO Drawer 7580, the University of Texas, Austin, TX 78713; tel: (512) 471-0112, fax: (512) 471-8883, e-mail: [email protected].

Sponsored Recommendations

Cat 6A Frequently Asked Questions

April 29, 2024
At CommScope we know about network change and the importance of getting it right. Conclusion Category 6A cabling and connectivity.

Revolutionize Your Network with Propel Fiber Modules

Oct. 24, 2023
Four sizes of interchangeable Propel fiber modules provide the breadth of capabilities for virtually any configuration.

Elevate Your Network with Propel High-Density Panels

Oct. 24, 2023
Propel high-density panels are designed to adapt and grow as your needs change.

Constellation™ - Explore power and data products

Oct. 24, 2023
Discover the Essentials for Building Your Power and Data System!