25-pair Category 5 Cabling

Feb. 1, 1997
Q: Who can I contact, or where can I get more information concerning the installation of 25-pair Category 5 cabling? I`m in the process of designing cabling- installation specifications that will be incorporated into all new and renovated building projects on my base. I have read all of the tia/eia-568a, eia/tia-569, tia-eia-606, tia/eia-607, TSB 67, and TSB 75 standards, and I understand that the standards are currently under revision. However, I cannot find references to installing 25-pair cab

Q: Who can I contact, or where can I get more information concerning the installation of 25-pair Category 5 cabling? I`m in the process of designing cabling- installation specifications that will be incorporated into all new and renovated building projects on my base. I have read all of the tia/eia-568a, eia/tia-569, tia-eia-606, tia/eia-607, TSB 67, and TSB 75 standards, and I understand that the standards are currently under revision. However, I cannot find references to installing 25-pair cable; that is, information on good installation practices.

I am planning to terminate all of the unshielded twisted-pair (UTP) horizontal cabling to a patch panel, then have another patch panel with a 25-pair Category 5 cable terminated on the back of it, feeding to Category 5-rated 66-type connecting blocks. This configuration would allow for the interface of telephone equipment. The only experience I have with this type of installation is what I have read. Can you help?

Ellis F. Baumer

US Air Force

Vandenberg AFB, CA

A: For installation guidance on 25-pair Category 5 cable, you need to contact the cable manufacturer. You are correct that some of the standards are currently under revision, but that is always the case. For example, tia/eia-568a was published in October 1995 and the Telecommunications Industry Association (TIA) TR41.8.1 working group has balloted three addenda and already begun work on tia/eia-568b.

As for your proposed design, it violates the tia/eia-568a, Annex E link model. There are too many pieces of termination hardware in the link. For a good overview of design methods, I suggest that you read the bicsi (Tampa, FL) Telecommunications Distribution Methods Manual (tdmm).

Sponsored Recommendations

imVision® - Industry's Leading Automated Infrastructure Management (AIM) Solution

May 29, 2024
It's hard to manage what you can't see. Read more about how you can get visiability into your connected environment.

Global support of Copper networks

May 29, 2024
CommScope designs, manufactures, installs and supports networks around the world. Take a look at CommScope’s copper operations, the products we support, our manufacturing locations...

Adapt to higher fiber counts

May 29, 2024
Learn more on how new innovations help Data Centers adapt to higher fiber counts.

Going the Distance with Copper

May 29, 2024
CommScopes newest SYSTIMAX 2.0 copper solution is ready to run the distanceand then some.