Conduit-fill limit

May 1, 1998
Q: eia/tia-569, Table 4.4-1, "Conduit Sizing," indicates cable fill, but nowhere in the standard is there an indication of the basis of the table for design. The Telecommunications Distribution Methods Manual of bicsi (Tampa, FL), in Issue 7, Chapter 4, page 41, repeats this table and provides notes that indicate the presumption of a design basis. Where does the 15% reduction per bend discussed here originate? It is not from nfpa-70 or eia/tia-569. I find the calculation in Note 2 suspect. It co

Q: eia/tia-569, Table 4.4-1, "Conduit Sizing," indicates cable fill, but nowhere in the standard is there an indication of the basis of the table for design. The Telecommunications Distribution Methods Manual of bicsi (Tampa, FL), in Issue 7, Chapter 4, page 41, repeats this table and provides notes that indicate the presumption of a design basis. Where does the 15% reduction per bend discussed here originate? It is not from nfpa-70 or eia/tia-569. I find the calculation in Note 2 suspect. It comes up with a similar answer to that found by using nfpa 70-1996, Chapter 9, Table 4, in the section for "Electrical Metallic Tubing," under the column headed "2 Wires, 31% Sq. In."

What do you think? Does the conduit-fill limit specified in the National Electrical Code (nec) apply to cabling referenced in Chapter 8, even though Sections 90-3 and 300-1 (a), Exception 5, appear to indicate otherwise? And if so, why is bicsi using the 40% conduit-fill limit?

Tim Quiring

Indiana University

Bloomington, IN

A: The basis for the conduit-fill limit is that it worked for power cable, so it will work for telecommunications cable as well. I suspect that the 15% reduction per bend originated when a group of building industry consultants got together in a Lexington, KY, tobacco barn in the 1970s, but I will have to confirm this with a few of those who may have been there. The "tobacco-barn science" involved a 100-foot length of conduit with a 90o bend at each end. The test was conducted by pulling the cable until it broke and recording the pulling tension--data from which many of today`s conduit-fill and pulling-tension guidelines were later derived.

The answer to your question about cabling in Chapter 8 is: "No." Chapter 8 covers communications systems and is independent of the other chapters in the nec, except where they`re specifically referenced. So why is bicsi us-ing the 40% figure? See my comment on the basis for the conduit-fill limit, above.

Sponsored Recommendations

What you need to know about 6A cabling

Aug. 3, 2022
Did you know that Category 6A cable is the best choice for structured cabling?

Cat 6A Hard Facts

Aug. 3, 2022
At CommScope we know about network change and the importance of getting it right. Conclusion Category 6A cabling and connectivity.

Why CommScope 6A?

Nov. 7, 2022
Inside buildings and across campuses, network demands and economics are changing. As applications like IoT, 10GBASE-T, multigigabit Wi-Fi 6/6E/7 and PoE++ become more common, ...

Smart Building Smart Cabling Case Study

Aug. 3, 2022
Located in the Shenzhen Nanshan Science and Technology Park is a building known as the citys landmark for new science and technology the Tencent Binhai Building (TBB).