Category 8 Questions Answered

Oct. 1, 2015
Standards experts provide insight into the forthcoming specification’s details, likely applications, and relationship to the work of other standards bodies.

Compiled by Patrick McLaughlin

As the Telecommunications Industry Association (TIA) TR-42.7 Subcommittee works diligently toward finalizing the specifications for Category 8 twisted-pair cabling systems, we asked several members of the subcommittee to answer some questions about Category 8.

Q: Can you provide a summary of how a Category 8 cabling system’s capabilities compare to those of previous-generation twisted-pair cabling systems, such as Category 6, 6A, 7, 7A, etc.? Please address bandwidth, channel configuration, and channel distance, as well as other performance characteristics you deem appropriate. Please describe how, if at all, the TIA is approaching backward compatibility between Category 8 and previous-generation twisted-pair systems.

Answer provided by Mark Dearing, senior product manager with Leviton Network Solutions: Since Category 5e was introduced in 1999, one of the constants in structured cabling has been the 100-meter, 4-connector channel. As data rates have increased, one of the primary differences between category systems is the frequency at which the signal is transmitted over the cable.

Category 7/7A offers a 100-meter 4-connector channel using shielded cabling, and has been designed to transmit signals at a frequency of 1000 MHz. Even though Category 7/7A operates at the higher frequency, there is no corresponding improvement in data rate over Category 6A because 10GBase-T is still the fastest twisted-pair-based data rate recognized by IEEE 802.3. Therefore, even if a Category 7/7A cabling system is installed, any available active equipment would be limited to 10-Gbit/sec performance. Category 7/7A is not a recognized category by TIA.

Category 8 is a significant departure from previous systems in that it uses a frequency of 2000 MHz, and is limited to a 30-meter 2-connector channel. Unlike Category 5e through Category 6A, which could use either unshielded twisted-pair (UTP) or shielded cable construction, Category 8 will require shielded cabling. The most likely cable construction for Category 8 will be 22-AWG S/FTP cabling.

Category 8 is also unique in that the ISO standard will recognize two different classes of product. (This topic is covered in greater detail later in this article.) Class I is based on the traditional RJ45 connector, while Class II will accept non-RJ45 connectors similar to Category 7/7A. While both solutions will offer backward compatibility in terms of transmitting the lower category data rates (1G or 10G), the Class I solution offers a migration path using the RJ45 connector platform. For example, a customer might install a Category 8 jack-to-jack link now, but continue to use Category 6A patch cords until the active equipment is upgraded. While the ISO standard includes both classes, the TIA Category 8 standard will only recognize a Class I solution.

Q: Given Category 8’s capabilities, where and how is it most likely to be deployed (e.g. in a data center vs. a corporate LAN, top-of-rack vs. end-of-row architectures)?

Answer provided by Masood Shariff, engineering senior principal with CommScope: Category 8 cabling is designed to support emerging IEEE 25GBase-T and 40GBase-T needed as server-to-access-switch interconnect applications. This need has been identified and available, or under development, over optical fiber links for longer reach (up to 500 meters), or twinax links for short reach (up to 7 meters).

The opportunity for balanced twisted-pair as a cost-effective viable media option for the intermediate distance needs between 5 and 30 meters, sufficient to serve 20 cabinets or racks in a data center, led to the initiation and development of both the IEEE 802.3 application standards and the associated TIA as well as ISO/IEC Category 8 cabling standards.

Q: What communication or collaboration is taking place between the TIA and the IEEE-particularly the 802.3bq Task Force-to ensure the TIA’s Category 8 specifications are in concert with the IEEE’s 40GBase-T and 25GBase-T specifications?

Answer provided by Masood Shariff: The IEEE 802.3bq Task Force is collaborating with TIA TR-42.7 and ISO/IEC/JTC 1/SC 25/WG3 to ensure consistency and compatibility of the cabling specifications within the “link segment” specifications in IEEE 802.3bq applications. Liaison letters to clarify requirements or provide additional information are generated at most meetings and latest drafts of the TIA and ISO Category 8 specifications are sent to the IEEE 802.3bq committee, where they are posted in a “private,” password-protected area for members to review and comment. The relationship between IEEE 802.3bq and its companion cabling standards organizations has been very positive and constructive, with several common members attending the meetings.

Q: Can you explain the relationship between the TIA and ISO/IEC groups working to define Category 8 cabling specifications? Specifically, how are the two groups’ efforts similar and how do they differ from each other? Observers of the standards-creation processes see terms like “Class II,” “Category 8.1,” and “Category 8.2.” The meanings of these terms are not necessarily self-evident.

Answer provided by Valerie Maguire, director of standards and technology with Siemon: The Telecommunications Industry Association (TIA) TR-42 Telecommunications Cabling Systems Engineering Committee and the joint technical committee of the International Organization for Standardization and the International Electrotechnical Commission (ISO/IEC JTC 1) share similar missions of developing, maintaining, and promoting standards related to information and communications technology. However, while TIA standards represent the consensus positions of their North American corporate constituents, ISO/IEC JTC1 standards represent the consensus positions of their member countries. As a result, voting within these organizations is also different, with TIA recognizing one vote per member company and ISO/IEC recognizing one vote per member country (i.e. North America only has one vote). A voting practice that accommodates regional preferences is the key reason why there are additional shielded options, such as Category 7A/Class FA specified in ISO/IEC standards compared to TIA standards.

While specifications for same-bandwidth balanced twisted-pair copper cabling systems are well harmonized between TIA and ISO/IEC, there are a few differences that stand out-most notably the naming convention for these cabling systems. In ISO/IEC standards, structured cabling components (e.g. cables, connecting hardware, and patch cords) are characterized by a performance “category” and are mated to form a permanent link or channel that is described by a performance “class.” In TIA standards, components and cabling are both characterized by a performance “category.” ISO/IEC and TIA equivalent grades of cabling, arranged in order of increasingly more stringent transmission performance, are shown in the table.

Note that, although ISO/IEC Class I and TIA Category 8 cabling systems are specified to 2000 MHz, they will not be electrical supersets (i.e. exhibit superior performance) of ISO/IEC Class FA cabling up to 1000 MHz.

Both the ISO/IEC JTC1 and TIA TR-42 are developing requirements for the balanced twisted-pair media that will support the 25GBase-T and 40GBase-T applications that are currently under development by IEEE 802.3. ISO/IEC is developing requirements for Class I cabling constructed from Category 8.1 components, and Class II cabling constructed from Category 8.2 components. TIA is developing requirements for Category 8 cabling constructed from Category 8 components and is also undertaking an initiative to develop Class II cabling requirements that will harmonize with ISO/IEC. Class I and Category 8 cabling specifications support modular RJ45-style connectors. The performance associated with Class II cabling can only be realized when Category 8.2 cables are used in conjunction with non-RJ45 interfaces such as the Siemon TERA connector. Draft ISO/IEC Class I and II, and TIA Category 8 cabling specifications, are mature and currently circulating for industry comment and review.

Note that Class I, Class II, and Category 8 cabling is characterized to 2 GHz and intended to support 30-meter cabling channels that contain no more than two connectors. These channels and the emerging 25/40GBase-T applications that they support are specifically targeted for deployment at the data center “edge,” where server-to-switch connections are made. Data center designers who can arrange their rack and cabinet layouts to support maximum 30-meter channel connections at these locations today will be well-positioned to migrate to 25/40GBase-T when the technology becomes available.

Q: What steps can a customer take today to design their facilities in such a way that they are “future-ready” to install Category 8 when product becomes available?

Answer provided by Frank Straka, product development manager with Panduit: Category 8 is a 30-meter channel, comprising a 24-meter permanent link and up to 6 meters of patch cable. Therefore, when planning data centers with end-of-row or middle-of-row topologies, ensure that your jack-to-jack links are no more than 24 meters in length and that you do not need more than 6 meters of patch cords in total. What this means for patching is you could have two, 3-meter patch cords, a 1-meter and a 5-meter patch cord, or any combination that adds up to 6 meters or less.

For top-of-rack topologies, the 3-meter reach should be more than sufficient to cover any direct switch-to-server links, especially if the data center had been using technologies like SFP+ that have a reach limit of about 5 meters.

Q: How similar can we expect Category 8 products to be compared to jacks and plugs existing in the market today? Will products be field-terminable? And with Category 8 being a shielded technology, are there any anticipated concerns for installers?

Answer provided by Frank Straka: Category 8 products are anticipated to be significant upgrades over existing Category 6A products due to the 4-times increase in bandwidth. However, these upgrades will primarily occur internally to the jack and plug in order to meet that bandwidth. Externally, they will be about the same form and fit as prior category jacks. This makes sense, as they need to work with the same patch panels, switches, and other equipment with which users are familiar today.

Category 8 will be field-terminable. Now given that Category 8 is shielded, field-terminable, and with a very high bandwidth, expect there to be at least some improvements made to how jacks are terminated in the field to both meet this new bandwidth and to ensure a good bond with the shield. For many contractors, the biggest change will be going into a shielded system and ensuring that the cable is properly grounded. If we connector companies do our job right, grounding the Category 8 cables and connectors will be a seamless process for the installer.

Sponsored Recommendations

Power up your system integration with Pulse Power - the game-changing power delivery system

May 10, 2023
Pulse Power is a novel power delivery system that allows System Integrators to safely provide significant power, over long distances, to remote equipment. It is a Class 4 power...

Network Monitoring- Why Tap Modules?

May 1, 2023
EDGE™ and EDGE8® tap modules enable passive optical tapping of the network while reducing downtime and link loss and increasing rack space utilization and density. Unlike other...

400G in the Data Center

Aug. 3, 2022
WHATS NEXT FOR THE DATA CENTER: 400G and Beyond

The Agile and Efficient Digital Building

May 9, 2023
This ebook explores how intelligent building solutions can help businesses improve network infrastructure management and optimize data center operations in enterprise buildings...